Heat Source and Heating System Design Calculator

The following calculators can be used to create an approximate total heat out from radiators or circuits, that can be used to range rate or set modern boilers in order to improve efficiency. Shown further below will be articles to specific boilers to adjust the heating load total.

Instructions for use: Please first use the radiator output calculator to work out the watts produced by a radiator. Please note the delta T is defaulted to 50°C  ie operating on Flow, Return and Room Temperatures of 80°C, 60°C and 20°C respectively or 75°C,65°C,20°C respectively. You may change the Delta T to suit your calculations.

Radiator Output Calculator

You may also create a radiator schedule as shown below if it makes it easier for you to calculate.

Copy the radiator output to the boxes below to produce a total for the heating system.

Total Output Calculator

Appendix

Delta T (°C / K )Conversion Factor
50.05
100.123
150.209
17.500.257
200.304
22.50.355
250.406
27.500.461
300.515
32.50.572
350.629
37.50.689
400.748
42.50.810
450.872
47.50.936
501.000
551.132
601.267
651.406
701.549
751.694