FA and RESET button and fault indicator LED are flashing. After appliance switches off flame is detected
| Step | Check | Action | |
|---|---|---|---|
| 1. | Is the condensate trap blocked? | yes: | ▶ Switch OFF the appliance. ▶ Clean out condensate trap discharge pipe. ▶ Switch ON the appliance. ▶ Press the reset button for 3 seconds and release it. After releasing the appliance re-starts. FA? go to step 2 |
| no: | go to step 2 | ||
| 2. | Electrode assembly defective? ▶ Switch OFF the appliance. ▶ Remove electrode assembly. Electrode assembly burnt out? | yes: | ▶ Replace electrode assembly. ▶ Switch ON the appliance. ▶ Press the reset button for 3 seconds and release it. After releasing the appliance re-starts. FA? go to step 3 |
| no: | go to step 3 | ||
| 3. | Problem with flue? ▶ Check CO2 level in combustion air in the flue (with outer casing fitted). Is CO2 level above 0.2%? | yes: | There are flue gases in the combustion air. ▶ Check flue, clean if necessary. ▶ Press the reset button for 3 seconds and release it. After releasing the appliance re-starts. FA? go to step 4 |
| no: | go to step 4 | ||
| 4. | Is the gas valve damaged? | yes: | ▶ Switch OFF the appliance. ▶ Disconnect the boiler power connection. ▶ Turn off gas valve. ▶ Change the gas valve. ▶ Open the gas valve. ▶ Reconnect the appliance power connection. ▶ Switch ON the appliance. ▶ Check appliance for leaks. ▶ Press the reset button for 3 seconds and release it. After releasing the appliance re-starts. FA? go to step 5 |
| no: | go to step 5 | ||
| 5 | ▶ Switch OFF the appliance. ▶ Disconnect the boiler power connection. ▶ Check if the 20-pin connector lead assembly is damaged. | ▶ Change the connector lead assembly. ▶ Reconnect the appliance power connection. ▶ Switch ON the appliance. ▶ Press the reset button for 3 seconds and release it. After releasing the appliance re-starts. FA? go to step 6 |
|
| 6 | The PCB is damaged. | ▶ Make a note of the altered service settings. ▶ Switch OFF the appliance. ▶ Disconnect the boiler power connection. ▶ Change PCB control board. ▶ Reconnect the appliance power connection. ▶ Switch ON the appliance. ▶ Restore service settings previously noted down. |