ACH Rates CIBSE

RoomCategory ACategory BCategory CNotes
Lounge/sitting room1.5t1.0*0.5
Living room1.5t1.0*0.5
Breakfast room1.510.5
Dining room1.510.5
Kitchen2.0*1.5*0.5*
Family/breakfast room2.0*1.5*0.5
Hall210.5
Cloakroom/WC2.0*1.5*1.5*
Toilet3.0*1.5*1.5*
Utility room3.0*2.0*0.5*
Study1.51.50.5
Games room1.510.5
Bedroom110.5
Bedsitting room1.510.5
Bedroom, including en suite bathroom21.51
Internal room or corridor000
Bedroom/study1.51.50.5
Landing210.5
Bathroom3.0*1.5*0.5*
Shower room3.0*1.5*0.5*
Dressing room1.510.5
Store room10.50.5

Note:
Category A: Air change rates for older existing buildings (pre-2000). Those with several chimneys and/or subject to preservation orders may require greater infiltration allowance than shown above.
Category B: Air change rates for modern buildings (2000 or later) with double glazing and regulatory minimum insulation.
Category C: New (or existing) buildings constructed after 2006 and complying with all current building regulations.

*Where mechanical extract ventilation is to be installed in a room and the extract volume exceeds the natural infiltration, it is advisable to make due allowance for the air extracted from any connecting room or corridor.

*Where a room contains an open fire or chimney, due ventilation allowance must be made. See section 3.5.4.4.

Additional Research

  • ACH 0.5 for everything
  • BSEN 12831 , Estonian Government Rate
  • 0.6-0.75 for all properties
  • Blower Door Test 0.3 – 0.4 (average on evidence) – 0.6 max
  • Single Glazing 0.5